Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2022, 08:58 PM
  • 08 0409_08 0408_02082022_131557.mp4

Date
02/08/2022
W/O
931537
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00002
PipeID
P00462
Time
12:58 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9600
Sewer Name
08 DAVIDSON CITY TRUNK, SECTION 4
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
09
Purpose
Routine Assessment
Project
WO_931537_TV08009_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
18 in.
Upstream MH
08 0408
Downstream MH
08 0409
Dir. of Survey
Upstream
Length Surveyed
395.3 ft.
Total Length
395.3 ft.
Structural Index
2
Structural Quick
5141
Structural Rating
165
O&M Index
2
O&M Quick
312O
O&M Rating
161
Overall Index
2
Overall Quick
Overall Rating
326
Pipe schematic from manhole 08 0408 to 08 0409
MH: 08 0408MH: 08 0409upstream0 ft. MGO - General Observation - MISSING PIPE0 ft. MSA - Survey Abandoned - CAM BLKD BY DEBRIS0 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES0.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0.3 ft. HSV - Hole Soil Visible, at 12 o'clock, within 8 inches of joint: YES2.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.3 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: NO2.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN43.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN88.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"105.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"157.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"229.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN259.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN359.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"393.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start393.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start395.3 ft. MWL - Water Level, 15 %of cross sectional area395.3 ft. MGO - Reversal Inspection395.3 ft. AMH - Downstream Manhole, Survey Begins - 08 0408395.3 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (4)

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    165.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: NO

    393 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: NO

  • General Observation - MISSING PIPE

    395.3 ft. - General Observation - MISSING PIPE

  • Deposits Settled Other,  15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    395.3 ft. - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
393SSS
392.9TBOPEN
289.6TFC
36TFC
165.9TBOPEN
395.3MGOMISSING PIPE
2SSS
0MWL
351.4TFOPEN
2DAGS
0MGO
395DAGS
135.7TFOPEN
395.3MSACAM BLKD BY DEBRIS
0AMH08 0408
307TFC
393FM
395HSV
237.4TFC
0MWM
395.3DSZ

Properties (6)

additional_info
630074020822052
custom_field_two
5
customer
1
datetime
2022-02-08T12:58:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false