- Date
- 03/10/2022
- W/O
- 0931911
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00691
- PipeID
- P14318
- Time
- 2:38 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H3032
- Sewer Name
- 18 NORTH PLANT OUTFALL TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 20
- Purpose
- Capital Improvement Program Assesment
- Project
- 20220310MDM_NORTH_PLANT_OUTFALL_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- 18 0464
- Downstream MH
- 18 0463
- Dir. of Survey
- Downstream
- Length Surveyed
- 117.8 ft.
- Total Length
- 117.8 ft.
- Structural Index
- 2
- Structural Quick
- 413A
- Structural Rating
- 64
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 68
Pipe schematic from manhole 18 0464 to 18 0463 Observation photos (4)

5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

68 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H

115.8 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

115.8 ft. - Material Change, Reinforced concrete pipe - 1 SHORT SECTION