- Date
- 03/15/2022
- W/O
- 0926994
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00333
- PipeID
- P20070
- Time
- 3:45 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H3037
- Sewer Name
- A JOINT OUTFALL A - UNIT 3B
- City
- CARSON
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 14
- Purpose
- Capital Improvement Program Assesment
- Project
- 20220315MDM_JOINT_OUTFALL_A_UNIT_3B
- Material
- RCP-CTL
- Shape
- Square
- Height
- 114 in.
- Upstream MH
- B 0929
- Downstream MH
- B 0928
- Dir. of Survey
- Downstream
- Length Surveyed
- 23.9 ft.
- Total Length
- 23.9 ft.
- Structural Index
- 4
- Structural Quick
- 5141
- Structural Rating
- 11
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 11
Pipe schematic from manhole B 0929 to B 0928 Observation photos (5)

13.1 ft. - General Observation - NO TILES IN PLACE

13.1 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

13.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

13.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

20.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR