Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2021, 11:05 AM
  • 22 0506_22 0505_11172021_032017.mp4

Date
11/17/2021
W/O
921564
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00809
PipeID
P16845
Time
3:05 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9543
Sewer Name
22 HOLLENBECK STREET TRUNK
City
COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
32
Purpose
Routine Assessment
Project
RFIR_WO_921564_TV22184_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0505
Downstream MH
22 0506
Dir. of Survey
Upstream
Length Surveyed
352.4 ft.
Total Length
352.4 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
204
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
344
Pipe schematic from manhole 22 0505 to 22 0506
MH: 22 0505MH: 22 0506upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 22 05062.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish8.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"49.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"95.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"98 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"193.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"250.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"311.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"336.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start342.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"346.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES350.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start352.4 ft. MWL - Water Level, 5 %of cross sectional area352.4 ft. MWM - Water Mark, 35 %of cross sectional area352.4 ft. AMH - Downstream Manhole, Survey Begins - 22 0505

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    5.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    352.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
102.2TFA
257.1TFC
5.7CM
0MWL
303TFC
0MWM
254.4TFA
16.2CM
349.9CM
40.8TFA
2DAGS
159.2TFA
0AMH22 0505
344.2TFA
10.2TFC
352.4MGOCOCKROACHES IN MANHOLE
349.9DAGS
352.4AMH22 0506

Properties (7)

additional_info
630069111621204
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-17T03:05:54-08:00
documentation
PRO PIPE
is_lateral_inspection
false