Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2022, 08:12 AM
  • G 0153_G 0152_01262022_005508.mp4

Date
01/26/2022
W/O
931515
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01180
PipeID
P01476
Time
12:12 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9153
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_931515_TV01236_JAN2022
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
36 in.
Width
48 in.
Upstream MH
G 0153
Downstream MH
G 0152
Dir. of Survey
Downstream
Length Surveyed
369.6 ft.
Total Length
369.6 ft.
Structural Index
4
Structural Quick
4200
Structural Rating
8
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole G 0153 to G 0152
MH: G 0153MH: G 0152downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - G 01532 ft. MGO - General Observation - MAG COAT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start59 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"95.7 ft. MB - Missing Brick, from 09 to 12 o'clock100.5 ft. MB - Missing Brick, from 09 to 03 o'clock, Start - TILE108.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"366.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish366.3 ft. MB - Missing Brick, from 09 to 03 o'clock, Finish369.6 ft. AMH - Downstream Manhole, Survey Ends - G 0152

Observation photos (4)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Missing Brick, from 09 to 12 o'clock

    95.7 ft. - Missing Brick, from 09 to 12 o'clock

  • Missing Brick, from 09 to 03 o'clock, Start - TILE

    100.5 ft. - Missing Brick, from 09 to 03 o'clock, Start - TILE

Observations (13)

DistanceCodeObservation
2MGOMAG COAT
0MWL
369.6AMHG 0152
366.3DAGS
2DAGS
366.3MB
100.5MBTILE
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
108.2TFA
59TFA
95.7MB
0AMHG 0153

Properties (7)

additional_info
630138012522202
custom_field_three
MISSING TILE
custom_field_two
2
customer
1
datetime
2022-01-26T00:12:30-08:00
documentation
PRO PIPE
is_lateral_inspection
false