Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2022, 11:18 AM
  • G 0137_G 0136_02022022_033606.mp4

Date
02/02/2022
W/O
931515
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01180
PipeID
P01460
Time
3:18 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9858
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_931515_TV01236_JAN2022
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
36 in.
Width
18 in.
Upstream MH
G 0137
Downstream MH
G 0136
Dir. of Survey
Downstream
Length Surveyed
326.7 ft.
Total Length
326.7 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
12
Pipe schematic from manhole G 0137 to G 0136
MH: G 0137MH: G 0136downstream0 ft. AMH - Upstream Manhole, Survey Begins - G 01370 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 75 %of cross sectional area2 ft. MGO - General Observation - MAG COAT2 ft. MB - Missing Brick, from 09 to 03 o'clock, Start - TILE2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start326.7 ft. MB - Missing Brick, from 09 to 03 o'clock, Finish326.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish326.7 ft. AMH - Downstream Manhole, Survey Ends - G 0136

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Missing Brick, from 09 to 03 o'clock, Start - TILE

    2 ft. - Missing Brick, from 09 to 03 o'clock, Start - TILE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
326.7MB
0AMHG 0137
0MWL
0MGOCOCKROACHES IN MH
2MGOMAG COAT
2MBTILE
0MWM
326.7SAP
326.7AMHG 0136
2SAP

Properties (7)

additional_info
630138020122203
custom_field_three
MISSING BRICK/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-02-02T03:18:42-08:00
documentation
PRO PIPE
is_lateral_inspection
false