Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2022, 06:44 AM
  • 04 0072_04 0071_02152022_230128.mp4

Date
02/15/2022
W/O
936555
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11808
Time
10:44 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9872
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_936555_TV04009_FEB2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0071
Downstream MH
04 0072
Dir. of Survey
Upstream
Length Surveyed
273 ft.
Total Length
273 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
12
O&M Index
2
O&M Quick
3212
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 04 0071 to 04 0072
MH: 04 0071MH: 04 0072upstream0 ft. AMH - Upstream Manhole, Survey Ends - 04 00720 ft. MGO - General Observation - COCKROACHES IN MH2.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5.3 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES37.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"57.8 ft. RML - Roots Medium Lateral, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES57.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"96.5 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"99.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"116.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start132.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"140.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"157 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES160.5 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES171.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"179.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"210.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"218.7 ft. HSV - Hole Soil Visible, from 12 to 02 o'clock, within 8 inches of joint: YES221.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"221.2 ft. RML - Roots Medium Lateral, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES236.2 ft. RFL - Roots Fine Lateral, from 01 to 05 o'clock236.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"260.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"273 ft. MWL - Water Level, 5 %of cross sectional area273 ft. MGO - General Observation - COCKROACHES IN MH273 ft. MWM - Water Mark, 10 %of cross sectional area273 ft. AMH - Downstream Manhole, Survey Begins - 04 0071

Observation photos (10)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Roots Fine Lateral, from 01 to 05 o'clock

    36.8 ft. - Roots Fine Lateral, from 01 to 05 o'clock

  • Roots Medium Lateral, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES

    51.8 ft. - Roots Medium Lateral, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES

  • Hole Soil Visible, from 12 to 02 o'clock, within 8 inches of joint: YES

    54.3 ft. - Hole Soil Visible, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    112.5 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    116 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    156.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Lateral, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES

    215.2 ft. - Roots Medium Lateral, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    267.7 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    273 ft. - General Observation - COCKROACHES IN MH

Observations (27)

DistanceCodeObservation
132.2TFA
173.5TFA
176.5TFA
0MWL
54.3HSV
36.8RFL
12.8TFC
273AMH04 0072
267.7RFJ
0MGOCOCKROACHES IN MH
270.3CM
215.2RML
215.2TFA
156.5CM
93.5TF
235.8TFC
101.1TFC
112.5CL
140.6TFC
0MWM
62.7TFC
51.8TFA
51.8RML
0AMH04 0071
116CL
36.8TFA
273MGOCOCKROACHES IN MH

Properties (7)

additional_info
630138021522201
custom_field_three
CRACKS/HOLE
custom_field_two
1
customer
1
datetime
2022-02-15T22:44:35-08:00
documentation
PRO PIPE
is_lateral_inspection
false