- Date
- 02/02/2022
- W/O
- 931535
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00429
- PipeID
- P24799
- Time
- 11:18 PM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K9771
- Sewer Name
- 05 COLDEN AVENUE TRUNK
- City
- LOS ANGELES
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 09
- Purpose
- Routine Assessment
- Project
- RFIR_WO_931535_TV05360_JAN2022
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 05 2271
- Downstream MH
- 05 2563
- Dir. of Survey
- Downstream
- Length Surveyed
- 213.7 ft.
- Total Length
- 213.7 ft.
- Structural Index
- 3
- Structural Quick
- 4226
- Structural Rating
- 20
- O&M Index
- 2
- O&M Quick
- 2916
- O&M Rating
- 24
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 44
Pipe schematic from manhole 05 2271 to 05 2563 Observation photos (5)

2.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: NO - AT MOUTH OF PIPE

158.5 ft. - Water Level, Sag in pipe, 35 %of cross sectional area, Start

178.4 ft. - Alignment Left, 10 %, Start

182.4 ft. - Water Level, Sag in pipe, 40 %of cross sectional area, Start

209.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start