Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2022, 09:52 AM
  • 05 2286_05 2285_02022022_021347.mp4

Date
02/02/2022
W/O
931535
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00429
PipeID
P07409
Time
1:52 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9770
Sewer Name
05 COLDEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_931535_TV05360_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
8 in.
Upstream MH
05 2286
Downstream MH
05 2285
Dir. of Survey
Downstream
Length Surveyed
377.8 ft.
Total Length
377.8 ft.
Structural Index
3
Structural Quick
543B
Structural Rating
68
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
68
Pipe schematic from manhole 05 2286 to 05 2285
MH: 05 2286MH: 05 2285downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 22863 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: NO7.5 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"7.6 ft. MGO - General Observation - STAINING108.4 ft. BSV - Broken Soil Visible, from 08 to 04 o'clock, within 8 inches of joint: YES115.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES121.8 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES128.9 ft. BSV - Broken Soil Visible, from 08 to 04 o'clock, within 8 inches of joint: YES143.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start211.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish288.5 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES377 ft. MGO - General Observation - CHANNEL IN D/S MH 05.2285 HAS AGGREGATE PROJECTING377.8 ft. AMH - Downstream Manhole, Survey Ends - 05 2285

Observation photos (7)

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: NO

    3 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: NO

  • Broken Soil Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    108.4 ft. - Broken Soil Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    115.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    121.8 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Broken Soil Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    128.9 ft. - Broken Soil Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    143.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    288.5 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
7.6MGOSTAINING
0MWL
377MGOCHANNEL IN D/S MH 05.2285 HAS AGGREGATE PROJECTING
0MWM
108.4BSV
121.8B
3B
7.5TF
115.7CM
143.3CM
288.5CM
211.8CM
0AMH05 2286
128.9BSV
377.8AMH05 2285

Properties (8)

additional_info
630098020122202
custom_field_three
BROKEN PIPE
custom_field_two
1
customer
1
datetime
2022-02-02T01:52:29-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
28956