Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2022, 10:18 AM
  • 14 0535B_14 0535A_02082022_022733.mp4

Date
02/08/2022
W/O
936259
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18626
Time
2:18 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9866
Sewer Name
14 35TH STREET WEST TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_936259_TV14074_FEB2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
14 0535A
Downstream MH
14 0535B
Dir. of Survey
Upstream
Length Surveyed
207.3 ft.
Total Length
207.3 ft.
Structural Index
3
Structural Quick
3G2G
Structural Rating
200
O&M Index
2
O&M Quick
2G00
O&M Rating
80
Overall Index
2
Overall Quick
Overall Rating
280
Pipe schematic from manhole 14 0535A to 14 0535B
MH: 14 0535AMH: 14 0535Bupstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 0535B0.2 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0.3 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish205.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start205.3 ft. MGO - General Observation - 25% MAG COAT205.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start205.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start207.3 ft. MWL - Water Level, 25 %of cross sectional area207.3 ft. AMH - Downstream Manhole, Survey Begins - 14 0535A207.3 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWL
2DAGS
0AMH14 0535A
207.1MGOCONN @ MH 9 O'CLOCK/ACTIVE
207.3AMH14 0535B
204.3SAV
207MGOCONN @ MH 3 O'CLOCK/ACTIVE
2MGO25% MAG COAT
204.3DAGS
0MWM
2SAV
2SSS
204.3SSS

Properties (7)

additional_info
630138020722201
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
3
customer
1
datetime
2022-02-08T02:18:03-08:00
documentation
PRO PIPE
is_lateral_inspection
false