Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2022, 06:47 AM
  • 05 0640_05 0126_02012022_230441.mp4

Date
02/01/2022
W/O
931734
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00520
PipeID
P05865
Time
10:47 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9899
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
HAWTHORNE
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_931734_TV05343_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
10 in.
Upstream MH
05 0640
Downstream MH
05 0126
Dir. of Survey
Downstream
Length Surveyed
171.1 ft.
Total Length
171.1 ft.
Structural Index
2
Structural Quick
4235
Structural Rating
87
O&M Index
2
O&M Quick
2F00
O&M Rating
70
Overall Index
2
Overall Quick
Overall Rating
157
Pipe schematic from manhole 05 0640 to 05 0126
MH: 05 0640MH: 05 0126downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 06400 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. MGO - General Observation - STAINING2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start37.2 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Start71.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"74.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"75.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 4"78.3 ft. CS - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES102.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES106.4 ft. CS - Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES, Start110.5 ft. CS - Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish116.3 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES120.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES130.3 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start137 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish137 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start164.1 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish164.1 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Finish164.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start170.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish170.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish171.1 ft. AMH - Downstream Manhole, Survey Ends - 05 0126171.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (10)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Water Level, Sag in pipe, 10 %of cross sectional area, Start

    37.2 ft. - Water Level, Sag in pipe, 10 %of cross sectional area, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 4"

    75.9 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

    78.3 ft. - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    102.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES, Start

    106.4 ft. - Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    120.5 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    130.3 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    137 ft. - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    164.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
37.2MWLS
130.3CS
110.5CS
0MWM
0AMH05 0640
164.1FS
170.6DAGS
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
2MGOSTAINING
71.2TFC
164.1MWLS
171.1AMH05 0126
171.1MGOCONNECTION AT MH 3 O'CLOCK
120.5CL
102.8CL
170.6FM
137CS
2DAGS
75.9TB
164.1FM
0MWL
116.3DSC
74.2TFC
78.3CS
106.4CS
137FS

Properties (7)

additional_info
630098020122201
custom_field_three
CRACKS, FRACTURES
custom_field_two
2
customer
1
datetime
2022-02-01T22:47:40-08:00
documentation
PROPIPE
is_lateral_inspection
false