- Date
- 01/17/2022
- W/O
- 926863
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00728
- PipeID
- P15212
- Time
- 4:14 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9833
- Sewer Name
- 19 STUDEBAKER ROAD TRUNK
- City
- CERRITOS
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 19
- Page No.
- 04
- Purpose
- Routine Assessment
- Project
- RFIR_WO_926863_TV19061_DEC2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 19 0241
- Downstream MH
- 19 0242
- Dir. of Survey
- Upstream
- Length Surveyed
- 150.9 ft.
- Total Length
- 150.9 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 3
- O&M Quick
- 3121
- O&M Rating
- 5
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 5
Pipe schematic from manhole 19 0241 to 19 0242 Observation photos (3)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

13.4 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

150.9 ft. - Survey Abandoned - DUE TO ENCRUSTATION. REVERSAL COMPLETE.