Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2022, 05:42 AM
  • B 0836_B 0883_02172022_215525.mp4

Date
02/17/2022
W/O
936253
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00102
PipeID
P09128
Time
9:42 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9875
Sewer Name
B JOINT OUTFALL B - UNIT 7 RELIEF
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_936253_TV15084_FEB2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
57 in.
Upstream MH
B 0836
Downstream MH
B 0883
Dir. of Survey
Downstream
Length Surveyed
287.6 ft.
Total Length
287.6 ft.
Structural Index
2
Structural Quick
342K
Structural Rating
134
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
248
Pipe schematic from manhole B 0836 to B 0883
MH: B 0836MH: B 0883downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 08360 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start241.3 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES244.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES245.9 ft. CS - Crack Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES263.3 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES285 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish285.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish285.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish287.6 ft. AMH - Downstream Manhole, Survey Ends - B 0883287.6 ft. MGO - General Observation - ROACHES @ MH

Observation photos (8)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

    241.3 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    244.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES

    245.9 ft. - Crack Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

    263.3 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

  • General Observation - ROACHES @ MH

    287.6 ft. - General Observation - ROACHES @ MH

Observations (16)

DistanceCodeObservation
285.9CM
287.6AMHB 0883
241.3CS
0AMHB 0836
2DAGS
0MWL
0MGOROACHES @ MH
287.6MGOROACHES @ MH
285.9DAGS
263.3CS
2SSS
244.1CL
2CM
0MWM
285SSS
245.9CS

Properties (8)

additional_info
630138021722201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-02-17T21:42:50-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
32486