Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2022, 11:18 AM
  • F 0273_F 0272_01102022_035538.mp4

Date
01/10/2022
W/O
926767
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00040
PipeID
P10226
Time
3:18 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9822
Sewer Name
F JOINT OUTFALL F - UNIT 4 RELIEF
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
RFIR_WO_926767_TV02204_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
15 in.
Upstream MH
F 0273
Downstream MH
F 0272
Dir. of Survey
Downstream
Length Surveyed
88.5 ft.
Total Length
88.5 ft.
Structural Index
4
Structural Quick
5E3B
Structural Rating
225
O&M Index
2
O&M Quick
2B00
O&M Rating
34
Overall Index
3
Overall Quick
Overall Rating
259
Pipe schematic from manhole F 0273 to F 0272
MH: F 0273MH: F 0272downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 02732 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.5 ft. SZM - Surface Other Mechanical, from 08 to 04 o'clock, within 8 inches of joint: YES , Start - REINFORCEMENT BROKEN @ ONE END - HANGING.21.5 ft. SRCM - Surface Reinforcement Corroded Mechanical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CORRODED / MISSING PORTIONS OF REINFORCEMENT.85.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish85.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish85.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish85.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish85.2 ft. SZM - Surface Other Mechanical, from 08 to 04 o'clock, within 8 inches of joint: YES , Finish - REINFORCEMENT BROKEN - @ ONE END - HANGING.85.2 ft. SRCM - Surface Reinforcement Corroded Mechanical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - CORRODED / MISSING PORTIONS OF REINFORCEMENT.88.5 ft. AMH - Downstream Manhole, Survey Ends - F 0272

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.6 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
85.2SSS
2SSS
21.5SRCMCORRODED / MISSING PORTIONS OF REINFORCEMENT.
2DAGS
0MWL
85.2DAGS
10.6SRV
0MWM
85.2SRV
85.2SAP
12.5SZMREINFORCEMENT BROKEN @ ONE END - HANGING.
0AMHF 0273
88.5AMHF 0272
85.2SZMREINFORCEMENT BROKEN - @ ONE END - HANGING.
85.2SRCMCORRODED / MISSING PORTIONS OF REINFORCEMENT.
2SAP

Properties (8)

additional_info
630138011022003
custom_field_three
BROKEN,VISBLE.,MISNG.RENFRCMNT./PROJCTNG. AGREGAT.
custom_field_two
1
customer
1
datetime
2022-01-10T03:18:35-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31219