Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2022, 05:59 PM
Date
01/06/2022
W/O
0931657
Weather
Dry
Operator/Surveyor
SHIVDEV BRAR
Sewer ID
Z00594
PipeID
P12629
Time
9:59 AM
Certificate
SEE REMARK
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0385
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20220106SB_SIERRA_MADRE_TRUNK_SEC3_2A
Sewer Type
SS
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
15 0851
Downstream MH
15 0850
Dir. of Survey
Downstream
Length Surveyed
354.1 ft.
Total Length
354.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4132
O&M Rating
154
Overall Index
2
Overall Quick
Overall Rating
154
Pipe schematic from manhole 15 0851 to 15 0850
MH: 15 0851MH: 15 0850downstream0 ft. MGO - General Observation - CONNECTION IN MH AT 3 AND 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 0851,1021AM2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start37.4 ft. RML - Roots Medium Lateral, at 02 o'clock, 5 %, within 8 inches of joint: NO - IN SEWER TRUNK85.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS IN LATERAL85.9 ft. RMB - Roots Medium Barrell, at 02 o'clock, 20 %, within 8 inches of joint: NO110.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS IN LATERAL110.8 ft. RFL - Roots Fine Lateral, at 02 o'clock - ROOTS IN TRUNK135.2 ft. RML - Roots Medium Lateral, from 02 to 05 o'clock, 25 %, within 8 inches of joint: NO135.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS IN LATERAL187.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"194.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"241 ft. RFL - Roots Fine Lateral, from 09 to 10 o'clock242.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS IN LATERAL350.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish354.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0850, 1116 AM354.1 ft. MGO - General Observation - CONNECTION AT 3 O'CLOCK

Observations (19)

DistanceCodeObservation
350.8DAGS
2.5DAGS
0MGOCONNECTION IN MH AT 3 AND 9 O'CLOCK
241RFL
85.9TFROOTS IN LATERAL
194.4TF
0MWL
354.1AMH15 0850, 1116 AM
354.1MGOCONNECTION AT 3 O'CLOCK
135.2RML
135.2TFROOTS IN LATERAL
110.8TFROOTS IN LATERAL
37.4RMLIN SEWER TRUNK
242.6TFDROOTS IN LATERAL
0MWM
110.8RFLROOTS IN TRUNK
0AMH15 0851,1021AM
187.7TFA
85.9RMB

Properties (9)

additional_info
U-0618-0703002249, POST ROOT INSPECTION ONLY
custom_field_three
LINED PIPE, GREASE, SOME ROOTS
custom_field_two
4
customer
LACSD
datetime
2022-01-06T09:59:11-08:00
documentation
BRAR, FRANKLIN, RAMIREZ
is_lateral_inspection
false
lining
PVCP FOLDED/REFORMED
year_laid
20020918