Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2022, 08:21 PM
Date
01/07/2022
W/O
0931657
Weather
Dry
Operator/Surveyor
SHIVDEV BRAR
Sewer ID
Z00594
PipeID
P12633
Time
12:21 PM
Certificate
SEE REMARKS
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I 0386
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20220107SB_ARCADIA_SIERRA_MADRE_TRUNK_SEC_3_2A
Sewer Type
SS
Material
Vitrified Clay Pipe
Shape
Circular
Height
9.300000190734863 in.
Upstream MH
15 0847
Downstream MH
15 0846
Dir. of Survey
Downstream
Length Surveyed
178.2 ft.
Total Length
178.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2F00
O&M Rating
70
Overall Index
2
Overall Quick
Overall Rating
70
Pipe schematic from manhole 15 0847 to 15 0846
MH: 15 0847MH: 15 0846downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 0847, 1225 PM0 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start176.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish176.9 ft. MGO - General Observation - COCKROACHES THROUGHOUT REACH178.2 ft. MGO - General Observation - CONNECTION AT 3 O'CLOCK178.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0846, 1242 PM

Observations (8)

DistanceCodeObservation
2.1DAGS
0MWL
0AMH15 0847, 1225 PM
178.2MGOCONNECTION AT 3 O'CLOCK
176.9DAGS
178.2AMH15 0846, 1242 PM
176.9MGOCOCKROACHES THROUGHOUT REACH
0MWM

Properties (8)

additional_info
U-0618-0703002249
custom_field_three
LINED PIPE, GREASE
custom_field_two
4
customer
LACSD
datetime
2022-01-07T12:21:51-08:00
documentation
BRAR, FRANKLIN, RAMIREZ
is_lateral_inspection
false
lining
CIPP