Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2022, 10:02 AM
  • 05 0647_05 0645A_02012022_021434.mp4

Date
02/01/2022
W/O
931491
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00520
PipeID
P26222
Time
2:02 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9900
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_931491_TV05368_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
05 0647
Downstream MH
05 0645A
Dir. of Survey
Downstream
Length Surveyed
214.3 ft.
Total Length
214.3 ft.
Structural Index
3
Structural Quick
3J2H
Structural Rating
253
O&M Index
2
O&M Quick
2H00
O&M Rating
86
Overall Index
2
Overall Quick
Overall Rating
339
Pipe schematic from manhole 05 0647 to 05 0645A
MH: 05 0647MH: 05 0645Adownstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 05 06470 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - STAINING2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start35 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES47 ft. CS - Crack Spiral, from 09 to 01 o'clock, within 8 inches of joint: YES69.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"69.4 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES114.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES117.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"139.8 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES146.5 ft. CS - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES157.5 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start167.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"211.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish211.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish212 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish212 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish214.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN214.3 ft. AMH - Downstream Manhole, Survey Ends - 05 0645A

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    35 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 09 to 01 o'clock, within 8 inches of joint: YES

    47 ft. - Crack Spiral, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    114.3 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    139.8 ft. - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

    146.5 ft. - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    157.5 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (25)

DistanceCodeObservation
214.3MGOCONN @ MH 9 O'CLOCK/OPEN
214.3AMH05 0645A
2CM
157.5CM
114.3CL
212SSS
167.9TF
117.9TFC
139.8CS
69.4DSC
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
211.4DAGS
146.5CS
2SSS
211.4CM
35CL
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
69.3TFC
0AMH05 0647
47CS
2.2MGOSTAINING
2.2DAGS
0MWL
212CM
0MWM

Properties (7)

additional_info
630098013122201
custom_field_three
MULTIPLE CRACKS/SPALLING
custom_field_two
3
customer
1
datetime
2022-02-01T02:02:27-08:00
documentation
PROPIPE
is_lateral_inspection
false