Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2022, 10:15 AM
  • 05 0645A_05 0645_02012022_023451.mp4

Date
02/01/2022
W/O
931491
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00520
PipeID
P18907
Time
2:15 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9900
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_931491_TV05368_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
05 0645A
Downstream MH
05 0645
Dir. of Survey
Downstream
Length Surveyed
390.5 ft.
Total Length
390.5 ft.
Structural Index
2
Structural Quick
3F2O
Structural Rating
271
O&M Index
2
O&M Quick
2O00
O&M Rating
156
Overall Index
2
Overall Quick
Overall Rating
427
Pipe schematic from manhole 05 0645A to 05 0645
MH: 05 0645AMH: 05 0645downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 05 0645A0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - STAINING2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start6.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"7.9 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES22.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES29.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start57.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"99.4 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES109.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"138.2 ft. MGO - General Observation - ABANDONED MH196 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish203 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES205 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"275.1 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES307.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"349.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES359 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"364.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES378.5 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES387.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish388 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish390 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ABANDONED390 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ABANDONED390.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0645

Observation photos (10)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    7.9 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    22.6 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    29.4 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    99.4 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    203 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Settled Compacted,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    275.1 ft. - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    349.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    364.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

    378.5 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
205TFC
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
2.5MGOSTAINING
364.9FL
29.4CM
0AMH05 0645A
99.4CM
307.9TFC
0MWL
2.5DAGS
349.4CM
359TFC
275.1DSC
390.5AMH05 0645
22.6CL
6.6TFC
387.9DAGS
109.3TFC
203CS
378.5FS
0MWM
7.9CL
138.2MGOABANDONED MH
2SSS
196CM
57.8TFC
390MGOCONN @ MH 9 O'CLOCK/ABANDONED
390MGOCONN @ MH 3 O'CLOCK/ABANDONED
388SSS

Properties (7)

additional_info
630098013122201
custom_field_three
SPALLING/CRACKS
custom_field_two
2
customer
1
datetime
2022-02-01T02:15:45-08:00
documentation
PROPIPE
is_lateral_inspection
false