- Date
- 01/24/2022
- W/O
- 931491
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00520
- PipeID
- P05883
- Time
- 4:22 AM
- Certificate
- U-115-06022794
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K9711
- Sewer Name
- 05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
- City
- INGLEWOOD
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- RFIR_WO_931491_TV05368_JAN2022
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 05 0658
- Downstream MH
- 05 0657
- Dir. of Survey
- Downstream
- Length Surveyed
- 352.4 ft.
- Total Length
- 352.4 ft.
- Structural Index
- 2
- Structural Quick
- 3K2M
- Structural Rating
- 327
- O&M Index
- 2
- O&M Quick
- 2M00
- O&M Rating
- 140
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 467
Pipe schematic from manhole 05 0658 to 05 0657 Observation photos (5)

2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

10.5 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

27.7 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

45.6 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

48.6 ft. - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES