Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2022, 09:25 AM
  • 05 0651_05 0650_02012022_014434.mp4

Date
02/01/2022
W/O
931491
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00520
PipeID
P05876
Time
1:25 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9900
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_931491_TV05368_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
18 in.
Upstream MH
05 0651
Downstream MH
05 0650
Dir. of Survey
Downstream
Length Surveyed
358.3 ft.
Total Length
358.3 ft.
Structural Index
2
Structural Quick
5141
Structural Rating
227
O&M Index
2
O&M Quick
2M00
O&M Rating
142
Overall Index
2
Overall Quick
Overall Rating
369
Pipe schematic from manhole 05 0651 to 05 0650
MH: 05 0651MH: 05 0650downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - STAINING44.3 ft. FS - Fracture Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES52 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start54.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start54.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish81.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"105.7 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish115.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES122.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"155.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES172.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"202.4 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start222.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"225.2 ft. B - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES229.5 ft. B - Broken, from 11 to 01 o'clock, within 8 inches of joint: NO252.9 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish265.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"317.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"332.4 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES352.4 ft. CS - Crack Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES355.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish356 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish358.3 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/ACTIVES358.3 ft. MGO - General Observation - ROACHES @ MH358.3 ft. AMH - Downstream Manhole, Survey Ends - 05 0650358.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (11)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

    44.3 ft. - Fracture Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    52 ft. - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    54.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    115.6 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    155.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    202.4 ft. - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 12 to 03 o'clock, within 8 inches of joint: YES

    225.2 ft. - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 11 to 01 o'clock, within 8 inches of joint: NO

    229.5 ft. - Broken, from 11 to 01 o'clock, within 8 inches of joint: NO

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    332.4 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES

    352.4 ft. - Crack Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES

Observations (32)

DistanceCodeObservation
355.4DAGS
52FS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
81.3TFC
252.9FS
358.3MGOCONN @ MH 3 O' CLOCK/ACTIVES
358.3MGOROACHES @ MH
44.3FS
225.2B
172.7TFC
122.6TFC
54.9DAGS
202.4FS
265.8TF
332.4CL
2.2DAGS
352.4CS
155.4FL
115.6FL
358.3AMH05 0650
105.7FS
54.9DAGS
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
317.2TFC
0MWL
2.2MGOSTAINING
358.3MGOCONN @ MH 9 O'CLOCK/ACTIVE
222.7TFC
0MWM
229.5B
2SSS
356SSS

Properties (7)

additional_info
630098013122201
custom_field_three
FRACTURES, BOKEN
custom_field_two
1
customer
1
datetime
2022-02-01T01:25:31-08:00
documentation
PROPIPE
is_lateral_inspection
false