Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2022, 08:12 AM
  • 05 0642_05 0641_02012022_002804.mp4

Date
02/01/2022
W/O
931491
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00520
PipeID
P05867
Time
12:12 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9900
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
HAWTHORNE
Loc. details
Airport
Location Code
M
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_931491_TV05368_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
10 in.
Upstream MH
05 0642
Downstream MH
05 0641
Dir. of Survey
Downstream
Length Surveyed
256.9 ft.
Total Length
256.9 ft.
Structural Index
2
Structural Quick
2J00
Structural Rating
106
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
214
Pipe schematic from manhole 05 0642 to 05 0641
MH: 05 0642MH: 05 0641downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 06420 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start69.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"120.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"171.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"185.9 ft. CS - Crack Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES222.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"222.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO225 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES225.3 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start245.7 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish254 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish254.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish256.9 ft. AMH - Downstream Manhole, Survey Ends - 05 0641

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO

    222.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    225 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
185.9CS
0MGOCONN @ MH 9 O'CLOCK/CAPPED
2.1DAGS
120.8TFC
225.3DSC
254SSS
245.7DSC
0MWL
0MWM
256.9AMH05 0641
2SSS
0AMH05 0642
254.5DAGS
222.7TBA
0MGOCONN @ MH 3 O'CLOCK/CAPPED
69.9TFC
222.7CL
225CL
171.9TFC

Properties (7)

additional_info
630098013122201
custom_field_three
SPALLING/CRACKS
custom_field_two
3
customer
1
datetime
2022-02-01T00:12:26-08:00
documentation
PROPIPE
is_lateral_inspection
false