Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 8, 2022, 12:06 PM
  • 18 0467_18 0466_382022_043159.mp4

Date
03/08/2022
W/O
0931911
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00691
PipeID
P14322
Time
4:06 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3030
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
202200307MDM_NORTH_PLANT_OUTFALL_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
18 0467
Downstream MH
18 0466
Dir. of Survey
Downstream
Length Surveyed
278 ft.
Total Length
278 ft.
Structural Index
5
Structural Quick
5841
Structural Rating
46
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
46
Pipe schematic from manhole 18 0467 to 18 0466
MH: 18 0467MH: 18 0466downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:25AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE11.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open12.2 ft. MGO - General Observation - 30% MAG COAT12.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG13.9 ft. SRC - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR16.3 ft. SRC - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - LON CIRCUM REBAR21.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR22.4 ft. SRC - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: YES, Finish27.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR44.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open52.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUUM REBAR67.5 ft. MGO - General Observation - 70% MAG COAT67.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR70.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open73.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO85.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR95.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Active123 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open124.7 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR145.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open278 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE278 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR CORRODED278 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG

Observation photos (12)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - 30% MAG COAT

    12.2 ft. - General Observation - 30% MAG COAT

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    12.2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    13.9 ft. - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - LON CIRCUM REBAR

    16.3 ft. - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - LON CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    21.3 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    27.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • General Observation - 70% MAG COAT

    67.5 ft. - General Observation - 70% MAG COAT

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    67.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

    73.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    85.4 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    124.7 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

Observations (26)

DistanceCodeObservation
0AMH4:25AM
13.9SRCLONG CIRCUM REBAR
44.7TFOpen
73.2SRC
52.3SRCLONG CIRCUUM REBAR
67.5MGO70% MAG COAT
85.4SRCLONG CIRCUM REBAR
124.7SRCLONG CIRCUM REBAR
27.6SRCLONG CIRCUM REBAR
16.3SRCLON CIRCUM REBAR
70.7TFOpen
12.2MGO30% MAG COAT
22.4SRC
11.7TFOpen
95.1TFAActive
145.8TFOpen
12.2SAMSEVERE AGG
278SSSBLISTERING PEELING CONCRETE
0MWL
278SRCLONG CIRCUM REBAR CORRODED
0MWM
21.3SRCCIRCUM REBAR
2SSSBLISTERING PEELING CONCRETE
278SAMSEVERE AGG
123TFOpen
67.5SRCLONG CIRCUM REBAR

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2022-03-08T04:06:26-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false