Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2022, 09:56 AM
  • 22 0249_22 0248_01072022_022249.mp4

Date
01/07/2022
W/O
931878
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16531
Time
1:56 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9758
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_931878_TV22016_JAN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0249
Downstream MH
22 0248
Dir. of Survey
Downstream
Length Surveyed
293 ft.
Total Length
293 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
1
Overall Quick
Overall Rating
1
Pipe schematic from manhole 22 0249 to 22 0248
MH: 22 0249MH: 22 0248downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02494.4 ft. MGO - General Observation - LINED PIPE84.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.9 ft. RFL - Roots Fine Lateral, at 02 o'clock161.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"261.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"293 ft. AMH - Downstream Manhole, Survey Ends - 22 0248

Observations (10)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
293AMH22 0248
0MWL
4.4MGOLINED PIPE
0MWM
0AMH22 0249
261.4TF
84.9TF
161.9TF
84.9RFL

Properties (7)

additional_info
6300908010622201
custom_field_three
RFIR NO SEVERE DEFECTS. (LINED PIPE)
custom_field_two
3
customer
1
datetime
2022-01-07T01:56:11-08:00
documentation
PROPIPE
is_lateral_inspection
false