Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2022, 05:57 AM
  • 22 0257_22 0256_01062022_220634.mp4

Date
01/06/2022
W/O
931878
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16539
Time
9:57 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9758
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_931878_TV22016_JAN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0257
Downstream MH
22 0256
Dir. of Survey
Downstream
Length Surveyed
230.5 ft.
Total Length
230.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 22 0257 to 22 0256
MH: 22 0257MH: 22 0256downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 02570 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area3.8 ft. MGO - General Observation - LINED PIPE50.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"111.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"230.5 ft. AMH - Downstream Manhole, Survey Ends - 22 0256230.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observations (9)

DistanceCodeObservation
184.7TF
0AMH22 0257
3.8MGOLINED PIPE
0MWM
50.5TF
111.5TF
230.5AMH22 0256
230.5MGOCONNECTION AT MH 9 O'CLOCK
0MWL

Properties (7)

additional_info
6300908010622201
custom_field_three
RFIR NO SEVERE DEFECTS. (LINED PIPE)
custom_field_two
3
customer
1
datetime
2022-01-06T21:57:59-08:00
documentation
PROPIPE
is_lateral_inspection
false