Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 14, 2021, 05:37 AM
  • 08 0210_08 0209_12132021_221102.mp4

Date
12/13/2021
W/O
926526
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00010
PipeID
P00270
Time
9:37 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9565
Sewer Name
08 GRACE STREET TRUNK, SECTS 2&3
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_926526_TV08022_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
08 0210
Downstream MH
08 0209
Dir. of Survey
Downstream
Length Surveyed
320.3 ft.
Total Length
320.3 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
252
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
254
Pipe schematic from manhole 08 0210 to 08 0209
MH: 08 0210MH: 08 0209downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02100.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 06 o'clock, , within 8 inches of joint: NO3.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"88.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"130.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"177.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"213.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"254.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"281.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"300.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"318.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish320.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK320.3 ft. AMH - Downstream Manhole, Survey Ends - 08 0209

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 06 o'clock,  , within 8 inches of joint: NO

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 06 o'clock, , within 8 inches of joint: NO

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    130.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (22)

DistanceCodeObservation
320.3MGOCONNECTION AT THE MH 3 OC'LOCK
69.8TFC
0MGOCONNECTION AT THE MH 3 OC'LOCK
3.8FM
0MWM
0MWL
88.6TFC
171.4TFC
2.1DAGS
281.6TF
130.6TB
219.7TFC
0AMH08 0210
320.3AMH08 0209
127.4TFC
0.1MGOCONNECTION AT THE MH 9 OC'LOCK
47.1TFC
254.8TF
318.7FM
300.7TFC
213.1TFC
177.8TFC

Properties (7)

additional_info
630074121321201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-12-13T21:37:02-08:00
documentation
PROPIPE
is_lateral_inspection
false