Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 14, 2021, 11:19 AM
  • 08 0192_08 0191_12142021_032642.mp4

Date
12/14/2021
W/O
926526
Weather
Light Rain
Operator/Surveyor
B.FUGATE
Sewer ID
Z00010
PipeID
P00252
Time
3:19 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9565
Sewer Name
08 GRACE STREET TRUNK, SECTS 2&3
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926526_TV08022_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
10 in.
Upstream MH
08 0192
Downstream MH
08 0191
Dir. of Survey
Downstream
Length Surveyed
183.9 ft.
Total Length
183.9 ft.
Structural Index
4
Structural Quick
4F31
Structural Rating
149
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
153
Pipe schematic from manhole 08 0192 to 08 0191
MH: 08 0192MH: 08 0191downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 01920 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area4.1 ft. CM - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES26.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"70.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"154 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 03 o'clock, , within 8 inches of joint: YES154.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: YES157.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"158.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES183.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK183.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0191

Observation photos (2)

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    40.8 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    157.9 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (13)

DistanceCodeObservation
70.9TFC
0AMH08 0192
157.9TB
183.9MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM
154DAGS
40.8TB
158.1CL
0MWL
154.1DAGS
4.1CM
183.9AMH08 0191
26.2TF

Properties (7)

additional_info
630074121321201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-12-14T03:19:58-08:00
documentation
PROPIPE
is_lateral_inspection
false