Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 15, 2021, 09:23 AM
  • 03 0413_03 0412_11152021_013902.mp4

Date
11/15/2021
W/O
921607
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00373
PipeID
P05175
Time
1:23 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9535
Sewer Name
03 MARINA TRUNK, SECTION 4
City
LONG BEACH
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_921607_TV03163_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
03 0413
Downstream MH
03 0412
Dir. of Survey
Downstream
Length Surveyed
300 ft.
Total Length
300 ft.
Structural Index
3
Structural Quick
4B3H
Structural Rating
202
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
204
Pipe schematic from manhole 03 0413 to 03 0412
MH: 03 0413MH: 03 0412downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 03 04130 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area5.3 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start125.9 ft. FM - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES148.9 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"152.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"206.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES231.5 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start231.5 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish300 ft. AMH - Downstream Manhole, Survey Ends - 03 0412300 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED - VARIOUS DEBRIS IN AREA OF THIS CONNECTION.300 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    125.9 ft. - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    148.9 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    152.8 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    206.1 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    231.5 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
231.5FM
148.9TBC
206.1FL
0MGOCONNECTION AT THE MH 9 OC'LOCK
300AMH03 0412
125.9FM
300MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED - VARIOUS DEBRIS IN AREA OF THIS CONNECTION.
152.8TB
0AMH03 0413
5.3CM
0MWM
300FM
0MWL
231.5CM

Properties (7)

additional_info
630074111521001
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-11-15T01:23:56-08:00
documentation
PROPIPE
is_lateral_inspection
false