Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2022, 08:19 AM
  • 14 0239_14 1003_01062022_004141.mp4

Date
01/06/2022
W/O
931716
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00569
PipeID
P25747
Time
12:19 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9815
Sewer Name
14 AVENUE "H" TRUNK
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_931716_TV14038_JAN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
14 0239
Downstream MH
14 1003
Dir. of Survey
Downstream
Length Surveyed
584.8 ft.
Total Length
584.8 ft.
Structural Index
3
Structural Quick
5V3V
Structural Rating
1145
O&M Index
2
O&M Quick
2V00
O&M Rating
232
Overall Index
3
Overall Quick
Overall Rating
1377
Pipe schematic from manhole 14 0239 to 14 1003
MH: 14 0239MH: 14 1003downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 02390 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start19 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start581.8 ft. MGO - General Observation - REINFORCEMENT - MULTIPLE SEGMENTS DAMAGED / BROKEN & HANGING @ 12 O'CLOCK.582.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish582.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish582.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish582.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish584.8 ft. AMH - Downstream Manhole, Survey Ends - 14 1003584.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK.

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    19 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWL
582.4DAGS
19SRV
0AMH14 0239
584.8AMH14 1003
582.4SRV
2SSS
582.4SSS
2SAP
584.8MGOACTIVE CONNECTION AT MH 9 O'CLOCK.
0MWM
581.8MGOREINFORCEMENT - MULTIPLE SEGMENTS DAMAGED / BROKEN & HANGING @ 12 O'CLOCK.
582.4SAP
2DAGS

Properties (7)

additional_info
630138010522202
custom_field_three
BROKEN/ VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
1
customer
1
datetime
2022-01-06T00:19:25-08:00
documentation
PRO PIPE
is_lateral_inspection
false