Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 16, 2021, 08:55 AM
  • B 0698A_B 0698_12162021_010714.mp4

Date
12/16/2021
W/O
926783
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00110
PipeID
P09369
Time
12:55 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9650
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_926783_TV22155_DEC2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
54 in.
Upstream MH
B 0698A
Downstream MH
B 0698
Dir. of Survey
Downstream
Length Surveyed
172.5 ft.
Total Length
172.5 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
102
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
103
Pipe schematic from manhole B 0698A to B 0698
MH: B 0698AMH: B 0698downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 0698A2 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start12.5 ft. VC - Vermin Cockroach21.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"30.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"113.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.9 ft. MWM - Water Mark, 30 %of cross sectional area167.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.5 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish172.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK172.5 ft. AMH - Downstream Manhole, Survey Ends - B 0698

Observation photos (1)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
21.7TF
172.2MGOCONNECTION AT MH 9 O'CLOCK
0MWM
30.7TF
167.6TF
0MWL
12.5VC
156.9MWM
2SAP
114.9TF
113.4TFC
172.5AMHB 0698
0AMHB 0698A
171.5SAP

Properties (7)

additional_info
630098121521201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2021-12-16T00:55:31-08:00
documentation
PROPIPE
is_lateral_inspection
false