Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2021, 08:05 AM
  • 20 0298_20 0297_12282021_020526.mp4

Date
12/28/2021
W/O
926690
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00736
PipeID
P19264
Time
12:05 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9805
Sewer Name
20 AVENUE "Q" EXTENSION TRUNK
City
PALMDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
07
Purpose
Routine Assessment
Project
WO_926690_TV20035_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
20 0297
Downstream MH
20 0298
Dir. of Survey
Upstream
Length Surveyed
331 ft.
Total Length
331 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 20 0297 to 20 0298
MH: 20 0297MH: 20 0298upstream0 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - DUE TO DEBRIS. REVERSAL COMPLETE.0 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish6.4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS17.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"20.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"67.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"166.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"222.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"271.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"277.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"318.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"324.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"329 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start331 ft. MWM - Water Mark, 70 %of cross sectional area331 ft. MWL - Water Level, 60 %of cross sectional area331 ft. AMH - Downstream Manhole, Survey Begins - 20 0297

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start - DEBRIS

    324.6 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS

Observations (22)

DistanceCodeObservation
331DSZ
208.1TFC
53.4TFC
108.9TFA
324.6DSZDEBRIS
263.6TFA
331MSADUE TO DEBRIS. REVERSAL COMPLETE.
6.1TFC
102.4TFC
211.2TFA
12.4TF
313.9TFA
257.7TFC
0MWM
59.1TFA
2DAGS
331DAGS
164.6TFA
310.4TFC
158.6TFC
0MWL
0AMH20 0297

Properties (7)

additional_info
630138122721201
custom_field_three
DEBRIS
custom_field_two
2
customer
1
datetime
2021-12-28T00:05:18-08:00
documentation
PRO PIPE
is_lateral_inspection
false