Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2021, 07:21 PM
  • 29 0082_29 0081_12232021_113920.mp4

Date
12/23/2021
W/O
932071
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00265
PipeID
P23862
Time
11:21 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9706
Sewer Name
29 33RD STREET TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_932071_TV29073_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0082
Downstream MH
29 0081
Dir. of Survey
Downstream
Length Surveyed
326.4 ft.
Total Length
326.4 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
189
Pipe schematic from manhole 29 0082 to 29 0081
MH: 29 0082MH: 29 0081downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 00820 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area9.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"21.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"83.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"90.6 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"166.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"307.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"323.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.4 ft. AMH - Downstream Manhole, Survey Ends - 29 0081

Observation photos (2)

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    83.3 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    90.6 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

Observations (13)

DistanceCodeObservation
0MWM
326.4AMH29 0081
21.7TF
0AMH29 0082
90.6TB
307.8TF
166.6TFC
83.3TBA
0MGOCONNECTION AT THE MH 9 OC'LOCK
9.2CM
18.9TF
323.6CM
0MWL

Properties (7)

additional_info
630074122321062
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-12-23T11:21:44-08:00
documentation
PRO PIPE
is_lateral_inspection
false