Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2021, 06:20 PM
  • 29 0080_29 0079_12232021_104508.mp4

Date
12/23/2021
W/O
932071
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00265
PipeID
P23860
Time
10:20 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9706
Sewer Name
29 33RD STREET TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_932071_TV29073_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0080
Downstream MH
29 0079
Dir. of Survey
Downstream
Length Surveyed
331.1 ft.
Total Length
331.1 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
260
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
260
Pipe schematic from manhole 29 0080 to 29 0079
MH: 29 0080MH: 29 0079downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 00800 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK3.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start46.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"49.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"70.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"82.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"142.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"227.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"289.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"291.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"329 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish331.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK331.1 ft. AMH - Downstream Manhole, Survey Ends - 29 0079

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    142.4 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    227.4 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

Observations (16)

DistanceCodeObservation
331.1MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH29 0080
0MWL
289.1TF
82.1TFA
49.6TFA
142.4TB
46.9TF
227.4TB
331.1AMH29 0079
329FM
0MWM
70.2TF
0MGOCONNECTION AT THE MH 9 OC'LOCK
291.8TF
3.6FM

Properties (7)

additional_info
630074122321062
custom_field_three
CRACKS, FRACTURE
custom_field_two
2
customer
1
datetime
2021-12-23T10:20:55-08:00
documentation
PRO PIPE
is_lateral_inspection
false