Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 1, 2021, 06:17 AM
  • H 0632_H 0631_09302021_223439.mp4

Date
09/30/2021
W/O
916367
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00183
PipeID
P10953
Time
11:17 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9395
Sewer Name
H JOINT OUTFALL H - UNIT 7B
City
CITY OF INDUSTRY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_916367_TV15231_OCT2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0632
Downstream MH
H 0631
Dir. of Survey
Downstream
Length Surveyed
479.7 ft.
Total Length
479.7 ft.
Structural Index
2
Structural Quick
2Q00
Structural Rating
182
O&M Index
2
O&M Quick
2W00
O&M Rating
240
Overall Index
2
Overall Quick
Overall Rating
422
Pipe schematic from manhole H 0632 to H 0631
MH: H 0632MH: H 0631downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - H 06322 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING THROUGHOUT19.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start338.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"349.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS476.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish476.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish476.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish479.7 ft. AMH - Downstream Manhole, Survey Ends - H 0631479.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    19.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    479.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
19.9SSS
349.5DSZDEBRIS
0MWM
479.7AMHH 0631
338.9TFA
2DAGS
476.6SSS
479.7MGOCOCKROACHES IN MANHOLE
476.6DAGS
0MWL
0MGOCOCKROACHES IN MANHOLE
476.6DSZ
2MGOMAG COATING THROUGHOUT
0AMHH 0632

Properties (6)

additional_info
630069093021201
custom_field_two
3
customer
1
datetime
2021-09-30T23:17:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false