Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 1, 2021, 06:08 AM
  • H 0633_H 0632_09302021_221628.mp4

Date
09/30/2021
W/O
916367
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00183
PipeID
P10954
Time
11:08 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9395
Sewer Name
H JOINT OUTFALL H - UNIT 7B
City
CITY OF INDUSTRY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_916367_TV15231_OCT2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0633
Downstream MH
H 0632
Dir. of Survey
Downstream
Length Surveyed
214 ft.
Total Length
214 ft.
Structural Index
2
Structural Quick
2G00
Structural Rating
80
O&M Index
2
O&M Quick
2G00
O&M Rating
84
Overall Index
2
Overall Quick
Overall Rating
164
Pipe schematic from manhole H 0633 to H 0632
MH: H 0633MH: H 0632downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06330 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.9 ft. MGO - General Observation - MAG COATING THROUGHOUT10 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start211 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish211 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish214 ft. AMH - Downstream Manhole, Survey Ends - H 0632214 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    9.9 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    214 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
10SSS
211SSS
0MWL
0MWM
2DAGS
0AMHH 0633
214AMHH 0632
211DAGS
0MGOCOCKROACHES IN MANHOLE
9.9MGOMAG COATING THROUGHOUT
214MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
630069093021201
custom_field_two
3
customer
1
datetime
2021-09-30T23:08:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false