Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2021, 06:40 PM
  • H 0517_H 0516_11022021_105808.mp4

Date
11/02/2021
W/O
916367
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00183
PipeID
P10942
Time
11:40 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9269
Sewer Name
H JOINT OUTFALL H - UNIT 7B
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_916367_TV15231_OCT2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
45 in.
Width
45 in.
Upstream MH
H 0517
Downstream MH
H 0516
Dir. of Survey
Downstream
Length Surveyed
242.3 ft.
Total Length
242.3 ft.
Structural Index
2
Structural Quick
322G
Structural Rating
90
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
90
Pipe schematic from manhole H 0517 to H 0516
MH: H 0517MH: H 0516downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 05170 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area3 ft. MGO - General Observation - MAG COATING15.9 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 4"27.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start240.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish240.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish242.3 ft. AMH - Downstream Manhole, Survey Ends - H 0516242.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    27.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    31.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
27.3SAP
0MGOCONNECTION AT THE MH 3 OC'LOCK
240.1SAV
242.3AMHH 0516
31.2SSS
240.1SSS
0AMHH 0517
0MWL
0MWM
242.3MGOCONNECTION AT THE MH 3 OC'LOCK
3MGOMAG COATING
15.9TB

Properties (7)

additional_info
630074110221061
custom_field_three
SPALLING, AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-11-02T11:40:38-07:00
documentation
PRO PIPE
is_lateral_inspection
false