- Date
- 11/04/2021
- W/O
- 916367
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00183
- PipeID
- P10941
- Time
- 7:46 AM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K9271
- Sewer Name
- H JOINT OUTFALL H - UNIT 7B
- City
- CITY OF INDUSTRY
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 35
- Purpose
- Routine Assessment
- Project
- RFIR_WO_916367_TV15231_OCT2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 45 in.
- Width
- 45 in.
- Upstream MH
- H 0516
- Downstream MH
- H 0515
- Dir. of Survey
- Downstream
- Length Surveyed
- 239.3 ft.
- Total Length
- 239.3 ft.
- Structural Index
- 2
- Structural Quick
- 3E2H
- Structural Rating
- 183
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 183
Pipe schematic from manhole H 0516 to H 0515 Observation photos (2)

10.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

80.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start