Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 3, 2021, 03:32 PM
  • H 0510A_H 0510_11032021_074817.mp4

Date
11/03/2021
W/O
916367
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00183
PipeID
P10937
Time
8:32 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9270
Sewer Name
H JOINT OUTFALL H - UNIT 7B
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_916367_TV15231_OCT2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
45 in.
Width
45 in.
Upstream MH
H 0510A
Downstream MH
H 0510
Dir. of Survey
Downstream
Length Surveyed
289 ft.
Total Length
289 ft.
Structural Index
2
Structural Quick
3I2J
Structural Rating
260
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
260
Pipe schematic from manhole H 0510A to H 0510
MH: H 0510AMH: H 0510downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 0510A0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area9.9 ft. MGO - General Observation - MAG COATING10.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start287.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish287.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish289 ft. AMH - Downstream Manhole, Survey Ends - H 0510

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    36.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0AMHH 0510A
287.4SSS
36.4SAV
9.9MGOMAG COATING
10.4SSS
287.4SAV
0MWM
0MWL
289AMHH 0510

Properties (7)

additional_info
630074110321061
custom_field_three
SPALLING, AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-11-03T08:32:03-07:00
documentation
PRO PIPE
is_lateral_inspection
false