Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 23, 2021, 11:46 AM
  • 05 1724_05 1723_11232021_035748.mp4

Date
11/23/2021
W/O
921521
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00471
PipeID
P06951
Time
3:46 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9547
Sewer Name
05 LOMITA TRUNK
City
HARBOR CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Routine Assessment
Project
RFIR_WO_921521_TV05198_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
24 in.
Upstream MH
05 1724
Downstream MH
05 1723
Dir. of Survey
Downstream
Length Surveyed
234.6 ft.
Total Length
234.6 ft.
Structural Index
3
Structural Quick
4H2H
Structural Rating
276
O&M Index
2
O&M Quick
2H00
O&M Rating
92
Overall Index
3
Overall Quick
Overall Rating
368
Pipe schematic from manhole 05 1724 to 05 1723
MH: 05 1724MH: 05 1723downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 17242 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start141.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN232 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish232 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish234.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN234.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1723234.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
141.5TFOPEN
2SSS
0MWL
234.6MGOCONN @ MH 9 O'CLOCK/UNKNOWN
232SSS
232DAGS
0MWM
234.6AMH05 1723
234.6FM
2DAGS
0AMH05 1724
2.8FM

Properties (7)

additional_info
630074112221201
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-11-23T03:46:08-08:00
documentation
PROPIPE
is_lateral_inspection
false