Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 22, 2021, 09:34 AM
  • 05 1707_05 1706_11222021_014552.mp4

Date
11/22/2021
W/O
921521
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00471
PipeID
P06934
Time
1:34 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9546
Sewer Name
05 LOMITA TRUNK
City
HARBOR CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_921521_TV05198_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
8 in.
Upstream MH
05 1707
Downstream MH
05 1706
Dir. of Survey
Downstream
Length Surveyed
387.9 ft.
Total Length
387.9 ft.
Structural Index
4
Structural Quick
4N31
Structural Rating
311
O&M Index
2
O&M Quick
2N00
O&M Rating
154
Overall Index
3
Overall Quick
Overall Rating
465
Pipe schematic from manhole 05 1707 to 05 1706
MH: 05 1707MH: 05 1706downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 17072 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start385 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish385 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish387.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish387.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE387.9 ft. AMH - Downstream Manhole, Survey Ends - 05 1706387.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWL
387.9MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
5.5FM
0MWM
385DAGS
0AMH05 1707
2SSS
387.4FM
2DAGS
387.9AMH05 1706
385SSS
387.9MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (7)

additional_info
630074112221001
custom_field_three
MULTIPLE CONTINUOUS FRACTURES
custom_field_two
2
customer
1
datetime
2021-11-22T01:34:10-08:00
documentation
PROPIPE
is_lateral_inspection
false