Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2021, 11:34 AM
  • 05 1692_05 1688_11182021_034414.mp4

Date
11/18/2021
W/O
921521
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00471
PipeID
P06918
Time
3:34 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9545
Sewer Name
05 LOMITA TRUNK
City
HARBOR CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_921521_TV05198_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
05 1692
Downstream MH
05 1688
Dir. of Survey
Downstream
Length Surveyed
264 ft.
Total Length
264 ft.
Structural Index
3
Structural Quick
4H2I
Structural Rating
276
O&M Index
2
O&M Quick
2I00
O&M Rating
104
Overall Index
3
Overall Quick
Overall Rating
380
Pipe schematic from manhole 05 1692 to 05 1688
MH: 05 1692MH: 05 1688downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16922 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES56.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start108.6 ft. TSA - Tap Saddle Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"261 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish261 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish263 ft. MGO - General Observation - CONN @ MH 1 O'CLOCK/ABANDONED263 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE264 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish264 ft. AMH - Downstream Manhole, Survey Ends - 05 1688

Observation photos (2)

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    50 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    56.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
56.2FM
108.6TSA
263MGOCONN @ MH 1 O'CLOCK/ABANDONED
0MWL
261DAGS
50FM
263MGOCONN @ MH 9 O'CLOCK/ACTIVE
264FM
0MWM
2DAGS
261SSS
2SSS
264AMH05 1688
0AMH05 1692

Properties (7)

additional_info
630074111721202
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-11-18T03:34:08-08:00
documentation
PROPIPE
is_lateral_inspection
false