Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2022, 06:49 AM
  • 22 0301_22 0300_01112022_230828.mp4

Date
01/11/2022
W/O
932176
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00794
PipeID
P16588
Time
10:49 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9765
Sewer Name
22 CAMERON TRUNK, SECTION 4
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_932176_TV22008_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0301
Downstream MH
22 0300
Dir. of Survey
Downstream
Length Surveyed
345.3 ft.
Total Length
345.3 ft.
Structural Index
3
Structural Quick
433L
Structural Rating
210
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
210
Pipe schematic from manhole 22 0301 to 22 0300
MH: 22 0301MH: 22 0300downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 03010 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK4.3 ft. MGO - General Observation - LINK PIPE14 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES21.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start76.9 ft. FM - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES103.8 ft. MGO - General Observation - LINK PIPE109.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. MGO - General Observation - LINK PIPE147.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"169.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.6 ft. FM - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES198.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"245.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"268.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"300.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"320.3 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES320.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"337.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"345.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0300345.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    14 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

    76.9 ft. - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

    198.6 ft. - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    320.3 ft. - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
119.4MGOLINK PIPE
21.7CM
219.3TFC
76.9FM
169.4TFC
320.3FM
103.8MGOLINK PIPE
320.3TFC
0MWM
198.6FM
147.1TF
198.6TFC
345.3AMH22 0300
245.8TFC
14CM
0AMH22 0301
300.2TFC
4.3MGOLINK PIPE
0MWL
337.6TFC
268.4TFC
109.6TFC
345.3CM
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (7)

additional_info
630098011122202
custom_field_three
MULTIPLE CRACKS/FRACTURE
custom_field_two
3
customer
1
datetime
2022-01-11T22:49:07-08:00
documentation
PROPIPE
is_lateral_inspection
false