Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2021, 10:59 AM
  • 14 0255_14 0232_11292021_030313.mp4

Date
11/29/2021
W/O
921737
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00575
PipeID
P18283
Time
2:59 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9605
Sewer Name
14 NORTH SIDE TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_921737_TV14077_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0255
Downstream MH
14 0232
Dir. of Survey
Downstream
Length Surveyed
8.7 ft.
Total Length
8.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 14 0255 to 14 0232
MH: 14 0255MH: 14 0232downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 02550 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start8.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Finish8.7 ft. AMH - Downstream Manhole, Survey Ends - 14 02328.7 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 12 O' CLOCK

Observation photos (1)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 02 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
8.7AMH14 0232
0AMH14 0255
8.2DAE
8.7MGOCONNECTIONS IN MH AT BOTH 3 AND 12 O' CLOCK
2DAE
0MWL

Properties (6)

additional_info
630069112921001
custom_field_two
4
customer
1
datetime
2021-11-29T02:59:44-08:00
documentation
PRO PIPE
is_lateral_inspection
false