Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 22, 2021, 10:33 AM
  • E 0098_01 0185A_12222021_025015.mp4

Date
12/22/2021
W/O
926628
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00202
PipeID
P02149
Time
2:33 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9646
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926628_TV01237_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
01 0185A
Downstream MH
E 0098
Dir. of Survey
Upstream
Length Surveyed
160.8 ft.
Total Length
160.8 ft.
Structural Index
3
Structural Quick
4223
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 01 0185A to E 0098
MH: 01 0185AMH: E 0098upstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Ends - E 00980 ft. MGO - General Observation - CONNECTION AT MH 9 AND 12 O'CLOCK1.7 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish64.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"76.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"90.3 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start90.3 ft. FH2 - Fracture Longitudinal Hinge, 2, from 12 to 06 o'clock, within 8 inches of joint: YES, Finish101.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish101.3 ft. FH2 - Fracture Longitudinal Hinge, 2, from 12 to 06 o'clock, within 8 inches of joint: YES, Start101.3 ft. CL - Crack Longitudinal, at 06 o'clock, within 8 inches of joint: YES, Finish109.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"115.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. CL - Crack Longitudinal, at 06 o'clock, within 8 inches of joint: YES, Start120.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start141.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES160.8 ft. AMH - Downstream Manhole, Survey Begins - 01 0185A160.8 ft. MWL - Water Level, 5 %of cross sectional area160.8 ft. MWM - Water Mark, 5 %of cross sectional area

Observation photos (6)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    19.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    31.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    51.1 ft. - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Longitudinal Hinge, 2, from 12 to 06 o'clock, within 8 inches of joint: YES, Start

    59.5 ft. - Fracture Longitudinal Hinge, 2, from 12 to 06 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    70.5 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    160.8 ft. - General Observation - COCKROACHES IN MH

Observations (20)

DistanceCodeObservation
160.8MGOCOCKROACHES IN MH
0AMH01 0185A
0MWL
59.5CL
0MWM
160.8AMHE 0098
45.5TFC
40.3TFC
70.5FM
96TFC
59.5FH2
19.5CL
70.5FH2
51.1TFC
41.4CL
31.2CL
160.8MGOCONNECTION AT MH 9 AND 12 O'CLOCK
159.1FM
84.5TF
59.5CL

Properties (7)

additional_info
630138122121201
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-12-22T02:33:23-08:00
documentation
PRO PIPE
is_lateral_inspection
false