Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 22, 2021, 10:58 AM
  • 01 0185_01 0184_12222021_030826.mp4

Date
12/22/2021
W/O
926628
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00202
PipeID
P01226
Time
2:58 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9646
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926628_TV01237_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0185
Downstream MH
01 0184
Dir. of Survey
Downstream
Length Surveyed
144.5 ft.
Total Length
144.5 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 01 0185 to 01 0184
MH: 01 0185MH: 01 0184downstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 01855.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"35.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"46.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"49 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"54 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"69.6 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"88.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"93.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"143.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish144.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0184

Observation photos (2)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0MGOCOCKROACHES IN MH
88.2TFC
49TF
0MWM
54TBA
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
5.3FM
11.4TFC
93.3TFA
46.4TFC
35.7TFC
69.6TB
143.1FM
144.5AMH01 0184
0AMH01 0185

Properties (7)

additional_info
630138122121201
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2021-12-22T02:58:20-08:00
documentation
PRO PIPE
is_lateral_inspection
false