Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2021, 12:22 PM
  • 01 0205_01 0204_12212021_043043.mp4

Date
12/21/2021
W/O
926628
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00202
PipeID
P01247
Time
4:22 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9645
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926628_TV01237_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0204
Downstream MH
01 0205
Dir. of Survey
Upstream
Length Surveyed
179.6 ft.
Total Length
179.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 01 0204 to 01 0205
MH: 01 0204MH: 01 0205upstream0 ft. MGO - General Observation - CONNECTION AT MH 12 AND 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 01 02050 ft. MGO - General Observation - COCKROACHES IN MH1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish66.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"120.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"170 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start173.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start179.6 ft. MWL - Water Level, 25 %of cross sectional area179.6 ft. MWM - Water Mark, 50 %of cross sectional area179.6 ft. AMH - Downstream Manhole, Survey Begins - 01 0204179.6 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    9.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    179.6 ft. - General Observation - COCKROACHES IN MH

Observations (14)

DistanceCodeObservation
0MWL
179.6MGOCONNECTION AT MH 12 AND 3 O'CLOCK
5.8TFA
2DAGS
59.4TFA
179.6AMH01 0205
9.6CM
178.6CM
0MWM
113TF
178.6DAGS
0AMH01 0204
179.6MGOCOCKROACHES IN MH
0MGOCOCKROACHES IN MH

Properties (7)

additional_info
630138122021202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-12-21T04:22:43-08:00
documentation
PRO PIPE
is_lateral_inspection
false