Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2021, 12:08 PM
  • 01 0204_01 0203_12212021_042224.mp4

Date
12/21/2021
W/O
926628
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00202
PipeID
P01246
Time
4:08 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9645
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926628_TV01237_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0203
Downstream MH
01 0204
Dir. of Survey
Upstream
Length Surveyed
276.5 ft.
Total Length
276.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 01 0203 to 01 0204
MH: 01 0203MH: 01 0204upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 02040 ft. MGO - General Observation - COCKROACHES IN MH2.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish47.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"59.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"61.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"118.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"160.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"181.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"198.9 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"244 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"272.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start274.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start276.5 ft. MWM - Water Mark, 50 %of cross sectional area276.5 ft. MWL - Water Level, 25 %of cross sectional area276.5 ft. AMH - Downstream Manhole, Survey Begins - 01 0203

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    276.5 ft. - General Observation - COCKROACHES IN MH

Observations (18)

DistanceCodeObservation
95TFA
228.8TFA
214.6TFA
274.1CM
274.1DAGS
157.7TFA
116.4TBA
0MWM
32.5TFA
0MWL
3.9CM
0AMH01 0203
216.9TFA
2DAGS
276.5AMH01 0204
276.5MGOCOCKROACHES IN MH
77.6TFA
134.1TFA

Properties (6)

additional_info
630138122021202
custom_field_two
2
customer
1
datetime
2021-12-21T04:08:00-08:00
documentation
PRO PIPE
is_lateral_inspection
false