Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2021, 11:16 AM
  • 01 0203_01 0202_12212021_033149.mp4

Date
12/21/2021
W/O
926628
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00202
PipeID
P01245
Time
3:16 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9645
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926628_TV01237_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Square
Height
15 in.
Width
15 in.
Upstream MH
01 0203
Downstream MH
01 0202
Dir. of Survey
Downstream
Length Surveyed
334.5 ft.
Total Length
334.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 01 0203 to 01 0202
MH: 01 0203MH: 01 0202downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02030 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start5.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start115.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"131.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"177.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS184.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"229.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"248.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"302.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"331.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"332.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish332.8 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish332.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish334.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0202334.5 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    334.5 ft. - General Observation - COCKROACHES IN MH

Observations (24)

DistanceCodeObservation
231.8TFA
0MWM
229.5TFC
177.7DSZDEBRIS
332.8DAGS
0MWL
248.9TFA
5.7CM
332.8DSZ
243.1TFA
0AMH01 0203
334.5AMH01 0202
332.8CM
2DAGS
184.7TFA
0MGOCONNECTION AT MH 9 O'CLOCK
167TFA
119.4TFC
115.8TBA
331.8TFA
131.2TFC
0MGOCOCKROACHES IN MH
302.5TFC
334.5MGOCOCKROACHES IN MH

Properties (7)

additional_info
630138122021202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-12-21T03:16:32-08:00
documentation
PRO PIPE
is_lateral_inspection
false