Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2022, 10:03 AM
  • 01 0176A_01 0176_01072022_021024.mp4

Date
01/07/2022
W/O
926628
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00202
PipeID
P01210
Time
2:03 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9819
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_926628_TV01237_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
12 in.
Upstream MH
01 0176A
Downstream MH
01 0176
Dir. of Survey
Downstream
Length Surveyed
20.9 ft.
Total Length
20.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 01 0176A to 01 0176
MH: 01 0176AMH: 01 0176downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 0176A0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS18.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish18.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish18.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish20.9 ft. MGO - General Observation - COCKROACHES IN MH20.9 ft. AMH - Downstream Manhole, Survey Ends - 01 017620.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    20.9 ft. - General Observation - COCKROACHES IN MH

Observations (13)

DistanceCodeObservation
2DAGS
0AMH01 0176A
18.5CM
0MWL
20.9MGOCOCKROACHES IN MH
18.5DSZ
4.3CM
0MGOCONNECTION AT MH 3 O'CLOCK
10DSZDEBRIS
0MWM
20.9AMH01 0176
18.5DAGS
20.9MGOCONNECTION AT MH 9 O'CLOCK

Properties (7)

additional_info
630138010622202
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-01-07T02:03:54-08:00
documentation
PRO PIPE
is_lateral_inspection
false