Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2021, 11:09 AM
  • B 0567_B 0566_11192021_031622.mp4

Date
11/19/2021
W/O
922056
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00101
PipeID
P09115
Time
3:09 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9604
Sewer Name
B JOINT OUTFALL B - UNIT 7
City
ROSEMEAD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
26
Purpose
Routine Assessment
Project
WO_922056_TV15120_NOV2021
Sewer Type
Gravity
Material
CIP
Shape
Circular
Height
12 in.
Width
60 in.
Upstream MH
B 0566
Downstream MH
B 0567
Dir. of Survey
Upstream
Length Surveyed
129.9 ft.
Total Length
129.9 ft.
Structural Index
3
Structural Quick
3D2D
Structural Rating
125
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
125
Pipe schematic from manhole B 0566 to B 0567
MH: B 0566MH: B 0567upstream0 ft. AMH - Upstream Manhole, Survey Ends - B 05670 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK1.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.9 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish127.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start127.9 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start129.9 ft. MWM - Water Mark, 20 %of cross sectional area129.9 ft. MWL - Water Level, 10 %of cross sectional area129.9 ft. AMH - Downstream Manhole, Survey Begins - B 0566

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    129.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
0MWM
128SSS
129.9AMHB 0567
128SCP
129.9MGOCOCKROACHES IN MANHOLE
0MWL
2SSS
0AMHB 0566
129.9MGOCONNECTION AT MH 3 O'CLOCK
2SCP

Properties (7)

additional_info
630069111821201
custom_field_three
METAL PIPE CORROSION
custom_field_two
2
customer
1
datetime
2021-11-19T03:09:55-08:00
documentation
PRO PIPE
is_lateral_inspection
false