Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2022, 06:26 PM
  • 29 0268A_29 0268_01132022_104356.mp4

Date
01/13/2022
W/O
931728
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00550
PipeID
P24174
Time
10:26 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9768
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_931728_TV29063_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0268
Downstream MH
29 0268A
Dir. of Survey
Upstream
Length Surveyed
230.7 ft.
Total Length
230.7 ft.
Structural Index
2
Structural Quick
5124
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
15
Pipe schematic from manhole 29 0268 to 29 0268A
MH: 29 0268MH: 29 0268Aupstream0 ft. ACOM - Cleanout Mainline, Survey Ends - 29 0268A3.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"11.5 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"45.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"53.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"68.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"73.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES87.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"88.9 ft. JOM - Joint Offset Medium105 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"116.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES148.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"150.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"159.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"186 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES195.5 ft. JOM - Joint Offset Medium223.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES224.7 ft. B - Broken, from 12 to 12 o'clock, within 8 inches of joint: YES230.7 ft. AMH - Downstream Manhole, Survey Begins - 29 0268230.7 ft. MWM - Water Mark, 10 %of cross sectional area230.7 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (8)

  • Water Mark, 10 %of cross sectional area

    0 ft. - Water Mark, 10 %of cross sectional area

  • Broken, from 12 to 12 o'clock, within 8 inches of joint: YES

    6 ft. - Broken, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    7.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium

    35.2 ft. - Joint Offset Medium

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    44.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    114.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium

    141.8 ft. - Joint Offset Medium

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    156.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
0AMH29 0268
143.3TFC
230.7ACOM29 0268A
0MWM
6B
125.7TFC
82.6TFC
7.4CL
44.7CL
162.2TB
185.6TF
80TFC
156.8CL
114.3CL
71.3TF
141.8JOM
227TFC
219.2TF
35.2JOM
0MWL
177TFC

Properties (7)

additional_info
630138011322061
custom_field_three
BROKEN, CRACKS
custom_field_two
1
customer
1
datetime
2022-01-13T10:26:50-08:00
documentation
PROPIPE
is_lateral_inspection
false